Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 300/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO.
|
Items
|
Unit
|
Data
|
||
FN12-12D/630
|
FN12-12(R)D/630
|
||||
1
|
Rated voltage
|
KV
|
12
|
||
2
|
Rated frequency
|
Hz
|
50
|
||
3
|
Rated Current
|
A
|
630
|
1250
|
|
4
|
Lightning impulse withstand voltage
|
KV
|
To earth and phase to phase 75, isolation fracture 85
|
||
5
|
1 min power frequency withstand voltage
|
KA
|
To earth and phase to phase 42, isolation fracture 48
|
||
6
|
Rated thermal stability current
|
KA
|
20(4s)
|
||
7
|
Rated dynamic current
|
KA
|
50
|
||
8
|
Rated dosing current (peak)
|
KA
|
50
|
50
|
|
9
|
Rated short circuit breaking current (Expected value)
|
KA
|
|
31.5
|
|
10
|
Maximum at critical breaking current
|
A2S
|
According to the fuse characteristic curve
|
||
11
|
Minimum breaking current
|
KA
|
According to the fuse characteristic curve
|
||
12
|
Rated transfer current
|
KA
|
|
1.5
|
|
13
|
Maximum breaking current (reference value)
|
KA
|
1.8
|
||
14
|
Breaking the capacity of the no-load transformer
|
KVA
|
1250
|
||
15
|
Rated cable charging current
|
A
|
10
|
||
16
|
Rated active load current breaking times
|
Times
|
>100
|
||
17
|
The impactor touches the load switch opening time
|
S
|
|
>0.06
|
|
18
|
Earthing switch thermal stability current
|
KA
|
20(2S)
|
||
19
|
Earthing switch thermal stability current (peak)
|
KA
|
50
|
||
20
|
Motor operating power supply voltage
|
V
|
AC DC 110, 220
|